Power Source |
Usable Power Supply Unit: FV-200PS
24 V DC (operating range: 19.5 – 27 V), M3 screw terminal |
Current Consumption |
250 mA |
Emergency Announcement |
Alert (repeated continuously), Evacuation (repeated continuously), False (repeated continuously), and Clear (repeated continuously) |
Emergency Warning Language |
English (default) |
Audio Input |
Fireman’s microphone: -55 dB*, 600 Ω, unbalanced, XLR-3P connector |
Audio Output |
EV : -20 dB*, unbalanced, Removable terminal block (2 pins) |
Control Input |
FA Input : No-voltage make contact input, Open voltage : 24 V DC,
Short-circuit current: Under 5 mA, Removable terminal block (2pins) |
Control Output |
Control output : Relay contact output x 4, rated voltage : 24 V DC,R emovable terminal block (2 pins) |
Frequency Response |
20 Hz – 20 kHz, ±3 dB, 1 kHz |
Distortion |
Under 1% (1 kHz, rated output) |
Wave Format |
44.1 kHz sampling frequency, 16 bit PCM (monaural) |
Recording System |
USB data transfer from rear panel |
Maximum Recording Time |
6 minutes (use built in memory) |
Operation |
Alert announcement button, Evacuation announcement button, False announcement button, Clear announcement button, Stop announcement button |
LED Indicator |
Power (Green), Fire (Red), Alert announcement (Green), Evacuation announcement (Green), False announcement (Green), Clear announcement (Green), USB (Green) |
Operating Temperature |
0 ℃ to +40 ℃ |
Operating Humidity |
Under 90% RH (no condensation) |
Finish |
Front Panel : Aluminum, black, alumite |
Dimensions |
482 (W) × 100 (H) × 396.7 (D) mm |
Weight |
4.3 kg (with microphone) |
Accessory |
Removable terminal plug (2 pins) x 7, Fireman’s Microphone x 1, Instruction Manual x 1 |